| Power supply: |
Direct current |
| Working voltage: |
8.2 Vdc (1Kohm) |
| Switching distance (mm): |
1 |
| Output type: |
Namur |
| Hysteresis (%Sn): |
1 ÷ 10 |
| Max. switching frequency: |
2000 Hz |
| Repeatability (%Sn): |
<= 3 |
| Current absorption at 8.2V: |
Target detected <= 1 mA - Target not detected >= 3 mA |
| Led indicator: |
Present |
| Operating temperature limits: |
-25 ÷ +60 °C |
| Storage temperature limits: |
-30 ÷ +70 °C |
| IP rating: |
IP 67 |
| Housing material: |
Nickelled brass |
| Cable type: |
2x0.25 mm² PVC |
| Weight: |
65 g |
| Mechanical characteristics: |
M8x1 |
| Connection type: |
Cable 3 m |
| Explosive atmosphere type: |
Mixture Air/gas and/or Air/Dust |
| Equipment category: |
1G / 1D |
| Installation area: |
Gas: Zone 0, Zone 1 and Zone 2 - Dust: Zone 20, Zone 21 and Zone22 |
| Protection method: |
Intrinsically safe |
| Marking: |
Gas: II 1G Ex ia IIC T6 Ga - Dust: II 1D Ex ia IIIC T85°C Da -25< Ta |
| Safety information: |
Connection to certified intrinsically safe circuits only with the following values : Uo <= 17 V , |
| Conforming standard: |
EN60079-0, EN60079-11, EN60079-26 and EN60947-5-6 |
| EC-tipe examination certificate - ATEX: |
IMQ 13 ATEX 019 |
| Certificate of conformity (CoC) - IECEx: |
IECEx IMQ 13.0012X |